RECD Temperature Rises but Outlet Pressure Does Not: Interpreting the Pattern

A trend chart can unsettle an engineer faster than an alarm can. Two lines that “should” move together do not. The temperature at the retrofit emission control device (RECD) climbs steadily over twenty minutes, and the outlet pressure line sits flat, as if nothing happened. Is the pressure sensor stuck? Is the filter doing nothing? Is the temperature sensor lying?

Before deciding that something is broken, ask a better question: why would these two quantities move together in the first place? If the answer is “they would not, in this situation”, the pattern is not a contradiction at all. In many conditions the pattern is exactly what physics predicts. In others it points to a real fault. This article helps you tell the two apart.

We do it by working from first principles. First, we fix the vocabulary, because “outlet pressure” is used loosely. Then we set out the three relationships that determine what should happen to pressure when temperature changes. We list six variables that you need to read together, give four stories that explain the pattern, show an illustrative calculation, and finish with tests and a decision table. As always, the supplier’s data for your device takes priority over any general reasoning here.

First, fix the vocabulary

Three pressure readings are often mixed up.

Inlet pressure is the gauge pressure (relative to atmosphere) just before the filter.

Outlet pressure is the gauge pressure just after the filter. It includes the resistance of everything downstream: the rest of the pipe, the silencer, the stack and the outlet. It is usually small compared with inlet pressure, often a few kilopascals.

Differential pressure (ΔP) is inlet minus outlet. It is the pressure the filter itself uses up.

Most controllers report ΔP and one or both absolute readings. If your “outlet pressure” is actually a second transmitter on the outlet tap, it has its own range, resolution and response. If it is derived, as in a sensor that measures ΔP and a single absolute pressure, then the outlet value is a calculation and inherits the errors of both.

Temperature also has several meanings: inlet gas temperature, bed or filter-body temperature (if a sensor reaches into or against the core) and outlet gas temperature. They behave differently, especially in a regeneration, so name which one is rising before you interpret anything.

Three relationships that govern the pattern

Relationship 1: Pressure drop depends on flow first

For any given restriction, pressure drop rises with flow. In the turbulent flow typical of pipes, bends and silencers it rises roughly with the square of velocity. In the slow flow through the porous wall of a ceramic filter, it rises roughly in proportion to velocity. Either way, the main driver of pressure at a fixed set of components is how much gas is flowing, which on a generator is set by engine load, not by the temperature of the exhaust.

So if temperature rises while load is constant, flow (in mass terms) has not changed, and most pressure readings should not change much. If temperature rises because load rose, pressure should rise because flow rose, and the temperature is a companion rather than the cause.

Relationship 2: Hotter gas takes up more volume

Gas expands when it is heated. At a fixed mass flow, a hotter gas has a lower density and a higher velocity in the same pipe. Resistance downstream of the filter, where the flow is turbulent, depends on density times velocity squared. Because density falls in proportion to temperature (measured in kelvin) and velocity rises in proportion to it, their combination, density times velocity squared, rises roughly in proportion to absolute temperature.

This is a modest effect, but it is real. If gas at the outlet warms from 400 K to 600 K (about 127 °C to 327 °C) at the same mass flow, the downstream pressure drop could rise by about half. Heating from 700 K to 800 K raises it by roughly 14%. These are rough estimates for turbulent downstream resistance; your supplier’s data will be more precise. The point is that temperature can raise outlet pressure, but only by a fraction of itself, and the effect is easy to lose in a small absolute number or a coarse sensor.

Relationship 3: Soot burning lowers ΔP but does not change outlet pressure much

During a regeneration, soot burns and its resistance falls. ΔP falls as the cycle progresses. The outlet pressure, which is controlled by downstream resistance and flow, changes little. So the usual picture in a successful cycle is temperature up, ΔP down and outlet pressure roughly flat or slightly up. That pattern is, again, normal.

A forum discussion of vehicle filters summarises the interplay: differential pressure depends strongly on air mass flow, and also on temperature, because the ceramic’s porosity and the gas properties change. This matches our relationships, and shows why a pressure reading alone cannot be read without flow and temperature alongside it.

Six variables to read together

A single pair of lines tells you very little. The table lists the six variables that matter and what each tells you about the pattern. Pull all six from the controller log for the same period.

VariableWhat it tells youWhy it matters here
Engine load (kW or %)Mass flow of exhaustFlow drives pressure more than temperature does
Inlet gas temperatureHeat arriving at the filterA rise may come from load, a heater, burner or burn
Bed or outlet temperatureHeat inside or leaving the filterA rise during a cycle shows soot burning or heater action
ΔP across the filterFilter resistanceShould fall as soot burns; should be compared at a constant load
Outlet (gauge) pressureDownstream resistanceResponds to flow and to downstream temperature
Heater current or fuel doseWhether assisted heat is being addedSeparates heater-driven temperature rise from load-driven

Always add a seventh item to the notes: the sensor type, range and resolution for each of the pressure and temperature signals. A pressure transmitter with a 0 to 100 kPa range and 0.1% accuracy has an uncertainty of about 0.1 kPa, which can swamp a downstream change of a few tenths of a kilopascal.

Four stories that explain “temperature up, outlet pressure flat”

Most cases fit one of four stories. For each we give what you would expect to see in the other variables and what to do.

Story A: A heater-assisted cycle at steady load (normal)

What happens. Load is steady. The heater switches on, and inlet and bed temperatures rise over many minutes. Exhaust mass flow does not change. Outlet pressure is governed by downstream resistance at a constant mass flow, with a small rise as gas warms. ΔP falls as soot burns.

What you would see. Load flat. Heater current on. Inlet and bed temperature up. ΔP down. Outlet pressure flat or up slightly, possibly within sensor noise.

Verdict. Normal. A flat outlet pressure here is expected. The healthy sign is the falling ΔP.

What to do. Nothing, except to log the cycle and verify that ΔP at a comparable load falls and holds. See interpreting an RECD regeneration completion message.

Story B: Load fell as temperature rose (flow offset)

What happens. Temperature rises because of regeneration, but load or flow falls at the same time, for example because the building load dropped. Falling flow lowers pressure, and any small rise from heating is cancelled.

What you would see. Load falls during the period. ΔP and outlet pressure flat or falling despite rising temperature.

Verdict. Not a contradiction. The two effects offset each other.

What to do. Compare only periods at stable load, or normalise using the supplier’s flow-ΔP curve. See comparing RECD pressure readings at different generator loads.

Story C: The temperature rise is local, not bulk

What happens. A sensor placed against the heater element, the bed or a hot spot reports a high local temperature that says little about the gas stream as a whole. The bulk gas temperature and flow are not changing much, so downstream pressure is flat.

What you would see. The rising temperature comes from a sensor near the heater or core. Inlet gas temperature and outlet gas temperature rise little. Heater current is on.

Verdict. Normal if the sensor is meant to sit there, but it needs context. A sensor in the wrong place can mislead. See RECD temperature sensor placement.

What to do. Confirm which sensor is which, their positions and what each is meant to indicate. Compare against the commissioning data for a normal cycle.

Story D: The pressure measurement is not seeing the exhaust

What happens. The outlet pressure transmitter or its sensing line is blocked, leaking, full of condensate, frozen at a constant value, scaled wrongly or connected to the wrong tap. It reports a flat number whatever the exhaust does.

What you would see. The pressure line is suspiciously smooth, or perfectly flat with no noise, even when load changes and the engine pulses. It does not respond to a load step. An independent reading shows different values.

Verdict. A fault, not physics.

What to do. Test the instrument and line. Apply a known small pressure or compare with a portable gauge. See separating a sensor fault from an RECD performance problem, pressure sensors versus pressure switches and detecting missing data in RECD monitoring records.

An illustrative calculation: how much should outlet pressure move?

The numbers below are invented to show the logic and are not data for any product.

Assumptions. A set runs at steady 60% load. Exhaust mass flow is constant. Downstream of the filter, resistance is mostly turbulent and the outlet pressure at gas temperature 400 °C (673 K) is 2.4 kPa gauge. A heater-assisted regeneration raises outlet gas temperature to 500 °C (773 K) for fifteen minutes.

Step 1. Estimate the change in downstream pressure drop with temperature. For turbulent flow at constant mass flow, pressure drop rises roughly in proportion to absolute temperature.

Step 2. The temperature ratio is 773 ÷ 673 = 1.15.

Step 3. Expected outlet pressure: 2.4 × 1.15 = about 2.76 kPa, a rise of about 0.36 kPa.

Step 4. Compare with the sensor. If the outlet transmitter has a 0 to 10 kPa range and 0.5% of range accuracy, its uncertainty is about 0.05 kPa. A change of 0.36 kPa is visible but small. If the transmitter has a 0 to 100 kPa range and 0.5% of range accuracy, uncertainty is about 0.5 kPa, and the 0.36 kPa rise is lost in noise. The displayed trace would be “flat”.

Step 5. Now consider ΔP. If soot burning reduces ΔP from 58 to 36 mbar over the same period, that fall of 22 mbar (2.2 kPa) is several times larger than the 0.36 kPa outlet change. The informative signal in this cycle is ΔP, not outlet pressure.

The lesson. A flat outlet pressure during a regeneration at steady load is not surprising. It could be physics, sensor resolution, or both. Judging the cycle by the outlet pressure would be like judging a marathon by the runner’s watch.

When “flat” is a warning

The stories above are benign except for D. Some patterns merit concern even if they look like Story A at first sight.

  • Temperature rises but ΔP also stays flat. If a regeneration is supposed to burn soot, ΔP should fall. A flat ΔP with rising temperature suggests the heat is not reaching the soot, the soot is not burning or the ΔP sensor is faulty. See RECD regeneration not completing.
  • Temperature rises but ΔP rises too. A rising ΔP while the temperature climbs can mean something is blocking flow, such as a damper closing, a partly collapsed element or heavy oily soot packing. Compare with the engine back-pressure limit.
  • Temperature rises very fast and then falls sharply with a ΔP collapse. That is the signature of a violent burn, possibly with a cracked or melted core. See can repeated failed regeneration damage an RECD filter.
  • Outlet pressure is perfectly flat while load changes. The signal is not following flow, so the sensor or line is suspect.
  • Outlet temperature does not rise when inlet temperature does. Heat is being lost or a bypass exists, or the outlet sensor is wrong. See exhaust leaks around an RECD.
  • Temperature rise is smaller than in previous cycles for the same heater input. The heater may be weakening or insulation lost. See what a rising regeneration duration tells you.

A decision table

Use the table after you have pulled the six variables for the period in question.

LoadInlet TBed or outlet TΔPOutlet PHeater or doseLikely meaning
FlatUpUpDownFlat or slightly upOnNormal heater-assisted cycle (Story A)
FallingUpUpFlat or downFlat or downOn or offFlow offset (Story B)
FlatFlatUp locallyDownFlatOnLocal sensor near heater or bed (Story C)
VariesUpUpFlatPerfectly flat, noiselessAnyPressure measurement fault (Story D)
FlatUpUpFlatFlatOnSoot not burning, or ΔP sensor fault; investigate
FlatUpUpUpUpOnPossible flow restriction; check dampers, pressure budget
FlatUp fastSpike then dropCollapsesFlatOnPossible violent burn or core damage; stop and call supplier
FlatFlatFlatFlatFlatOffNothing happening; check why regeneration did not start

Tests that separate the stories

Several quick tests help you choose a story.

Test 1: Confirm which sensor is which. Read the commissioning sheet and the drawing and match each log channel to a physical sensor, its location, range and units. Mislabelled channels cause many apparent paradoxes.

Test 2: Check the pressure signal’s character. A real exhaust pressure signal has some noise and responds to load changes and pulses. A perfectly flat, noiseless line is suspicious. Zoom into the raw data at one-second resolution if possible.

Test 3: Apply a small known pressure change. With the system safe and the supplier’s agreement, apply a gentle pressure to the sensing line (a hand pump or a syringe, within the transmitter’s limits) and watch the reading follow. Do this only when the system is cold and isolated. A non-responsive reading indicates a blocked line or a stuck transmitter.

Test 4: Use an independent gauge. Connect a calibrated portable manometer to a spare tap and compare at steady load.

Test 5: Change the load in a controlled way. Make a modest load change under supervision and watch whether the outlet pressure follows. A real signal rises with load. See RECD alarm during generator load steps for how transients behave.

Test 6: Check the resolution and range. From the datasheet, compare the instrument’s uncertainty with the change you expect. If the expected change is smaller than the uncertainty, a flat trace tells you nothing, and a more sensitive instrument may be needed for that point.

Test 7: Compare with a known-good cycle. Overlay the problem cycle on a good one from the commissioning period or from a verified cycle. The difference, not the absolute shape, is the clue. See what an RECD regeneration history report should include.

Practical habits that prevent confusion

A worked illustration: reading one cycle end to end

The following is an illustrative scenario, not a real customer. An engineer at a warehouse reviews the log of a heater-assisted regeneration on a 250 kVA set and notices that bed temperature climbed from 380 to 590 °C over twenty-five minutes while outlet pressure stayed at about 1.9 kPa.

Step 1: the six variables. Load was steady at 52 to 54% throughout. Heater current was 8.7 A on each phase for the first twenty minutes, tapering after. Inlet gas temperature rose from 365 to 405 °C. Bed temperature rose from 380 to 590 °C. ΔP fell from 58 mbar to 36 mbar. Outlet pressure moved between 1.88 and 1.93 kPa.

Step 2: story A or something else? Load flat, heater on, bed temperature up, ΔP down, outlet pressure flat. This fits Story A.

Step 3: how much should outlet pressure have moved? Inlet gas temperature rose about 40 K on a base of about 640 K, a ratio of 1.06. The outlet gas is cooler than the bed, so its change is smaller. An expected rise of a few percent of 1.9 kPa is about 0.1 kPa, which is close to the 0.05 kPa uncertainty of the transmitter. A flat trace is within what the engineer would expect.

Step 4: independent check. To be safe, the engineer compares the outlet transmitter with a portable manometer during the next steady run. They agree within 0.05 kPa.

Step 5: verification. ΔP at 52% load at the next two runs is 35 and 36 mbar, near the post-cycle value, so the cycle worked.

Conclusion. The pattern that prompted the question was normal. The engineer notes in the log that outlet pressure is not a sensitive indicator of regeneration on this installation and that ΔP and bed temperature are the useful signals, and adds a line to the shift handover sheet so that the next person does not raise the same alarm. See the RECD shift handover log.

Frequently asked questions

Should outlet pressure rise when the filter gets hotter?

A little, at the same mass flow, because hot gas takes more volume and moves faster through the downstream pipework. The rise is usually small and can be lost in sensor resolution. The bigger driver is flow, which follows engine load.

What should I look at to judge a regeneration?

ΔP at a comparable load before and after, the temperature curve, heater behaviour, interruptions and whether the result persists. Outlet pressure is a supporting signal, not the main one.

Why is my outlet pressure perfectly flat?

Real exhaust pressure has some noise and responds to load. A perfectly flat trace suggests a blocked or leaking sensing line, a stuck transmitter, a wrongly scaled channel or a value that is calculated and not measured. Test the instrument.

Could a flat outlet pressure mean the filter is not blocked?

Outlet pressure does not tell you whether the filter is blocked. ΔP is the measure of the filter’s resistance. Outlet pressure reflects downstream resistance and flow.

Does the pattern matter for emission tests?

Tests need stable, documented conditions. Record load, temperatures and pressures during the test, and avoid sampling during or just after a regeneration unless the test plan says so. See RECD testing during regeneration: what to record.

Bringing it together

When temperature rises and outlet pressure does not, ask why the two would move together at all. Flow, set by engine load, drives pressure far more than temperature does. Temperature adds a modest rise downstream, soot burning lowers ΔP and not outlet pressure, and a coarse or faulty sensor can make a small change look like none. Read six variables side by side, match the pattern to one of four stories, test the instrument when the trace looks too smooth and judge regeneration by ΔP at a comparable load.

If you would like help reading a trend chart or deciding which signals your controller should log, see our retrofit emission control devices, the DG set emission regulations overview or contact the Aceget team.