You have found black, oily residue at the exhaust outlet. The DG set has spent months doing light-load test runs and short grid-failure starts. Now the RECD is struggling: differential pressure (ΔP) is high, regeneration cycles are slow or failing, and someone has said the words “wet stacking”.
At this point the RECD supplier and the engine specialist each hold half of the answer. The supplier understands the filter. The engine specialist understands why the engine produced the wet soot and whether it is still producing it. This article is written for the meeting between you and the engine specialist. It gives you twelve questions to ask, explains why each one matters for RECD regeneration after wet stacking, tells you what a good answer sounds like and ends with a recovery order that protects the filter.
Why wet stacking is a special problem for an RECD
Wet stacking is the build-up of unburnt fuel, oil and soot in the exhaust of a diesel engine that runs lightly loaded for long periods. At low load the combustion chambers stay cool, the fuel does not burn completely and the engine’s piston rings and cylinder walls may seal less well, so unburnt fuel and some lubricating oil pass into the exhaust as a sticky, oily mixture. Wikipedia’s article on wet stacking gives a short general description.
A particulate filter fed by an engine in this state sees something quite different from the dry, fluffy soot it is designed for.
- Oily soot is sticky. It packs densely into the filter walls and channel inlets, and it raises ΔP faster per gram than dry soot.
- It burns differently. The liquid fraction evaporates and may burn first, then the carbon behind it burns more slowly. During regeneration, the volatile material can produce smoke and a smell, and the heat release can be uneven.
- It coats a catalyst. Where the RECD has a catalyst, an oily film can mask active sites and delay ignition of the soot beneath. See catalyst poisoning in an RECD.
- It may be a symptom, not the cause. Wet stacking in an RECD-equipped set often means the duty cycle never gives the filter the exhaust temperature it needs. That is a feature of how the set is used, which an engine repair alone will not fix.
Our article on choosing an RECD for a generator running at low load explains the light-load problem from the buying side. This one begins after the problem has occurred.
How to use the twelve questions
Print the list. Send it to the engine specialist before the visit so they can bring the right tools and records. Write the answers beside each question, and keep the sheet with the maintenance file. The questions fall into four groups:
- Group A, finding out how bad it is (questions 1 to 3)
- Group B, finding out why it happened (questions 4 to 7)
- Group C, deciding what to fix first (questions 8 to 10)
- Group D, planning the return to service (questions 11 and 12)
Group A: How bad is it?
Question 1: “Is the engine currently producing wet or oily exhaust, or is this historical?”
Why it matters. If the engine is still producing oily exhaust, cleaning or regenerating the filter without fixing the source simply reloads it. If the problem is historical, the task is recovery only.
What a good answer looks like. The specialist checks the exhaust at a stable moderate load after a proper warm-up, inspects the outlet and any collected condensate, looks at the colour and smell of the exhaust, and checks the crankcase breather and intake for oil carry-over. They tell you whether oil is being burned, fuel is passing unburnt, or both.
Red flag. A confident answer given only from looking at the stack at idle.
Question 2: “How much oil and fuel have gone through, and where is it now?”
Why it matters. Unburnt fuel and oil can sit in the silencer, in the bellows, in low pipe sections and in the RECD housing. When the set finally runs hot, that liquid can ignite, smoke heavily or even flash. You need to know before you load the set.
What a good answer looks like. An inspection of drain points and low spots, a plan to drain and dispose of the liquid safely, and a check that the lagging and nearby cables are not soaked. Our guide to handling soot and ash removed during RECD servicing covers disposal and handling.
Red flag. “It will burn off by itself.”
Question 3: “Is there any sign of internal engine damage or contamination?”
Why it matters. Dilution of the lubricating oil by fuel and heavy soot loading of the oil can change its properties. Wet stacking may also coincide with glazed cylinder bores or sticking rings.
What a good answer looks like. Oil analysis (viscosity, fuel dilution, soot content, wear metals), a compression or blow-by check where appropriate, and a decision on oil and filter change before the engine runs for long at load.
Red flag. No oil sample and no change of oil planned.
Group B: Why did it happen?
Question 4: “What does the load profile say?”
Why it matters. The usual cause is duty, not a defect. A DG set that runs at 10 to 20% load for test runs, or that carries only a small building load, will run cool.
What a good answer looks like. The specialist asks for or reads the load history from the controller or a logger, divides run hours into load bands and shows what share of hours fell below the engine’s recommended minimum. Our article on using DG load logs to assess RECD suitability shows a simple method for this.
Red flag. A diagnosis made without any load data.
Question 5: “Are the injectors, turbocharger and air supply in good condition?”
Why it matters. Worn or leaking injectors, poor spray patterns, a lazy turbocharger or a restricted air filter all make a diesel burn fuel poorly, even at normal load. They can turn a mild light-load issue into a serious one.
What a good answer looks like. An injector test or at least a balance check, turbo shaft play and boost check, inspection of the air filter and intercooler passages, and a statement about whether each is within the manufacturer’s limits.
Question 6: “What about fuel quality, fuel system leaks and fuel injection timing?”
Why it matters. Water or contaminated diesel, a leaking return line, or incorrect timing can all increase unburnt fuel and smoke.
What a good answer looks like. A fuel sample, a check for water in the tank, filter condition, and confirmation of timing or electronic control settings.
Question 7: “Is the cooling system keeping the engine too cold?”
Why it matters. A stuck-open thermostat or an over-large cooling system can keep the coolant temperature below its normal range, which makes light-load combustion worse.
What a good answer looks like. The specialist checks coolant temperature at a steady load against the manufacturer’s range, tests the thermostat and confirms that radiator shutters or fan controls work.
Group C: What should be fixed first?
Question 8: “In what order should we repair the engine side and the filter side?”
Why it matters. If you clean the filter first and the engine is still producing oily soot, the filter reloads. If you repair the engine first and leave a heavily loaded filter in place, you may get a violent regeneration. The order has to be planned.
What a good answer looks like. Usually: stop the problem running (reduce light-load running), fix engine-side faults, drain and clean contaminated pipework, then deal with the filter (cleaning, controlled regeneration or replacement), then verify. Your own case may differ, so the specialist and RECD supplier should agree the sequence in writing.
Question 9: “Is it safe to attempt regeneration now, and under what conditions?”
Why it matters. Oily soot can behave unpredictably. A regeneration started on a filter that is very heavily loaded or oil-soaked risks high temperatures and smoke. Repeated failed attempts carry their own risks; see can repeated failed regeneration damage an RECD filter.
What a good answer looks like. A clear yes or no based on ΔP and inspection, with conditions if yes: stable load, no operator interruptions, someone watching temperatures, a limit on attempts and a stop rule. If the specialist is unsure, they say so and defer to the RECD supplier.
Question 10: “Should the filter be cleaned, baked, or replaced?”
Why it matters. A filter loaded with oily soot may clean up completely, or the oil may have penetrated deep into the substrate and coated the catalyst. Cleaning methods differ, and not every method suits every filter.
What a good answer looks like. The specialist defers to the RECD supplier for the decision and does not improvise. Where a service workshop is used, the right question is whether their process suits the filter type and what they will report afterwards. See RECD filter core versus complete assembly replacement and the guide to refurbished RECD filter core reuse.
Red flag. A suggestion to burn the filter out by running the set at full load “for an hour” without any monitoring.
Group D: Returning to service
Question 11: “What load and run pattern will keep the engine and the filter healthy from now on?”
Why it matters. Without a changed duty pattern, wet stacking returns.
What a good answer looks like. A concrete plan: minimum load for test runs (for example, run on a load bank or a real load rather than idling), maximum idle time, test duration, scheduling on cooler days if heat is an issue, and who is responsible. Our article on restarting a DG set with an RECD after long inactivity offers a loaded warm-up approach, and the guide to RECDs on generators that run occasionally explains why this matters.
Question 12: “What will we measure to prove the problem is solved?”
Why it matters. “It seems better” is not a result.
What a good answer looks like. A short list: ΔP at a stated reference load, exhaust temperature at the RECD inlet, time to reach working temperature, oil analysis after a set number of hours, and regeneration cycle records for the next three cycles. Agree the pass criteria before work starts.
The data pack to bring to the meeting
The specialist can answer these twelve questions far better with documents in hand. Gather the following.
| Item | Why it helps |
|---|---|
| DG nameplate details and engine make, model and serial number | Identifies service limits and parts |
| Run hours and service history, including oil and filter changes | Shows oil and maintenance pattern |
| Load history or at least typical loads for test runs and outages | Answers Question 4 |
| RECD model, installation date and commissioning baseline (ΔP, temperatures) | Gives before-and-after comparison |
| Regeneration log for the last six to twelve months | Shows cycle trends; see what a regeneration history report should include |
| Photographs of the exhaust outlet, silencer drains and RECD housing | Shows contamination without a visit |
| Fuel purchase source and any recent changes | Helps Question 6 |
| Any alarms, trips or smoke complaints | Gives timeline |
If your RECD records are thin, start collecting now. Our post on what to record in an RECD event log gives a working list.
A recovery order that protects the filter
The sequence below is a general template. Your supplier and engine specialist must adapt it, but the logic usually holds.
Step 1: Stop making it worse
Stop idling or very light running for test purposes. If the set must run, run it on a real or load-bank load at a level the engine manufacturer recommends. If you do not have a load bank, hire one for the recovery period.
Step 2: Make the area safe
Look for fuel or oil pooling in silencers, low pipe sections, drain points and the filter housing. Drain it using the procedure your site and supplier agree. Remove soaked insulation or oily rags, which are a fire risk. Make sure the set cannot be started casually during this work.
Step 3: Repair the engine-side cause
Carry out whatever the specialist’s tests suggest: injector service, air filter, thermostat, fuel system, oil and filter change, and so on.
Step 4: Plan the filter treatment
With the RECD supplier, decide whether the filter should be regenerated under supervision, removed for cleaning or replaced. Use ΔP and inspection to decide. Do not guess.
Step 5: Run a loaded warm-up
Bring the set up to working temperature at an appropriate load in steps, and watch ΔP, inlet temperature and exhaust. The aim is to reach a stable working temperature and watch for steady ΔP behaviour. For a detailed approach, see restarting a DG set with an RECD after long inactivity.
Step 6: Run a supervised regeneration, if the plan calls for it
Pick a time when the load is stable and the set cannot be interrupted. Have the supplier on the phone or on site. Record start and end ΔP, peak temperature, duration and any smoke or smell.
Step 7: Verify with agreed measures
Compare the measures from Question 12 against the pass criteria. If they fail, go back to Step 3 rather than repeating Step 6.
Step 8: Change the routine
Update the test-run procedure, load targets and log sheets. The recovery is only permanent if the routine changes.
A worked scenario: the commercial building that tested too gently
The following is an illustrative example. A commercial building runs a 250 kVA DG set. Every Saturday the facilities team starts the set for a 20-minute test with no load transfer, so it idles. During a monsoon month the grid fails four times, each time for under 30 minutes at about 15% load. Operators notice oily droplets at the exhaust outlet, and the RECD’s ΔP at idle rises from 21 mbar to 38 mbar over eight weeks.
The meeting. The engine specialist works through the twelve questions. Oil analysis shows a small amount of fuel dilution. The injectors and turbo are within limits. The load history shows that 85% of the hours in the last six months were below 20% of rating. The thermostat is working. The diagnosis: duty cycle, not engine defect.
The plan.
- Switch weekly tests to load transfer on a real building load of at least 40%, for 45 minutes.
- Change the oil and filter now.
- Drain and clean the silencer and exhaust low point.
- Ask the RECD supplier to supervise a regeneration after a loaded warm-up.
- Review ΔP at a reference load after two weeks.
The outcome (illustrative). ΔP at the reference load falls to about 27 mbar after the supervised cycle and holds there. The cost of the visit and the oil change is modest compared with replacing a filter core. The key change is the test routine, and without it the problem would have returned within a season.
Common mistakes after wet stacking
- Treating it as a filter problem only. The engine and the duty cycle are part of the cause.
- Regenerating before draining and inspecting. Pooled liquid can cause smoke or ignition.
- Idling “to warm it up”. Long idling makes wet stacking worse.
- Skipping the oil analysis. Fuel-diluted oil harms the engine, and the result guides the repair.
- Using fuel additives as a shortcut. Our article on whether diesel fuel additives can replace an RECD explains why additives are not a substitute for diagnosis.
- No written pass criteria. Without them the job never officially finishes.
FAQ
Does wet stacking permanently ruin an RECD?
Not necessarily. Many filters recover after the engine-side problem is fixed, contamination is drained and the filter is cleaned or regenerated under supervision. Permanent damage is more likely if oily soot has been burned off violently or the catalyst has been coated for a long time.
Can I just run the DG at full load to burn it off?
That is risky without guidance. A heavy oily load burning at once can create high temperatures and smoke, and your generator may not tolerate extended full load. Follow the plan agreed with the RECD supplier and engine specialist.
How do I know if wet stacking is happening?
Common signs include black oily residue or droplets at the exhaust outlet, oily smell, smoke at low load, soot-soaked silencer drains and rising ΔP at low loads. A professional inspection confirms it.
How much load is enough to avoid wet stacking?
The engine manufacturer’s recommended minimum load applies. Generator makers commonly describe a set as lightly loaded below about 30% of rated load (Generac FAQ), and Kohler’s long-standing advice is to exercise sets at about 30% of rated capacity or the manufacturer’s stated minimum (Kohler white paper). Where your engine’s minimum is higher than 30%, or your RECD supplier asks for more, follow that.
Who should I call first, the engine specialist or the RECD supplier?
Call both and ask them to share findings. The engine specialist explains why the soot was oily. The supplier explains what the filter can safely tolerate. Having both on a call before work starts avoids contradictory instructions.
Will warranty be affected?
Warranty depends on the terms. Document duty, service history and the steps taken. Our article on RECD warranty terms explains what usually matters, and the guide to what to record for an RECD warranty claim helps you prepare.
Bringing it together
RECD regeneration after wet stacking succeeds when the engine-side cause is found, the contaminated components are drained and cleaned, the filter is treated under supervision and the routine of how the set is run is changed. Take the twelve questions to the engine specialist, bring the data pack, agree the order of work with the RECD supplier and write down the measures that will show success.
If you need help matching an RECD to a set with a light-load duty, browse our retrofit emission control devices, read the FAQ or contact the Aceget team.
[…] Electric heater. At light load, exhaust flow is low and cool. Heater energy has less gas to heat, which in some designs makes light-load regeneration easier, but the soot is often wetter, which complicates burning. See RECD regeneration after wet stacking. […]
[…] Wet stacking leaves sticky deposits; see RECD regeneration after wet stacking […]
[…] glazed or fused. Wet stacking leaves an oily soot layer that clings to the walls; our article on RECD regeneration after wet stacking describes how it arises. High-temperature events can sinter ash into harder masses. The cleaning […]