Nothing on the skid looks different after an RECD firmware update. The filter housing is the same, the wiring is the same, the controller panel has the same badge on its door. Yet the logic deciding when an alarm fires, how a sensor voltage becomes a pressure reading, and what number travels to your building management system (BMS) may all have been rewritten in fifteen minutes on a technician’s laptop.
That is why a firmware change deserves the same respect as a design change. It is one, only invisible. If a technician plans to “just update the software” at the next visit, here are the questions to put to them, and to the supplier, in writing before you agree.
The questions run as an interview in five rounds: why, what changes, how, what if, and after. Each has a note on why it matters and what a good answer sounds like. A checklist, a verification table, a change record template and a worked units example follow.
A Short Primer: What Firmware in an RECD Controller May Do
Not every retrofit emission control device has a controller. Many RECDs in India are passive units, and some carry only a gauge or pressure switch. If yours has no programmable controller, this article mostly does not apply. For a refresher on the main design families, see our guide on how an RECD works.
Where an RECD does have a controller with updatable firmware, that firmware may handle some or all of the following, depending on design:
- Reading sensors, such as differential pressure (ΔP) across a filter element and exhaust temperatures upstream or downstream.
- Scaling values, converting a 4–20 mA or voltage signal into engineering units like kPa, mbar or °C.
- Triggering alarms and warnings, for example high ΔP, high temperature, sensor fault or heater fault.
- Logging data, with timestamps, to internal memory, an SD card or a remote server.
- Controlling heaters or regeneration, where the design uses active regeneration or heated elements. The background on why regeneration matters is well covered in DieselNet’s overview of particulate filter regeneration.
- Communicating to a BMS, SCADA or remote monitoring platform over Modbus RTU, Modbus TCP or a supplier’s own protocol.
Every one of those functions can shift with a firmware release, sometimes as a side effect nobody mentioned.
Round 1: “Why” Questions
What problem does this firmware update fix?
Why it matters: “It is the latest version” is not a reason. If your controller is stable, an update adds risk for no visible benefit. A specific defect, such as a drifting clock or an overflowing log, is a reason you can weigh.
Good answer sounds like: “Version 2.3 fixes a fault where the high-ΔP alarm did not reset after regeneration on units with your sensor type. You reported two nuisance alarms last quarter that match this.”
Can we see the release notes?
Why it matters: Release notes are the only written record of what changed. Without them you cannot judge impact on alarms, BMS points or logs, or later prove what was done.
Good answer sounds like: “Yes, notes for every version from 2.1 to 2.3, with known issues.”
Is the update mandatory, recommended or optional?
Why it matters: A mandatory update usually signals a reliability defect you should understand. An optional one can wait for a planned shutdown when your BMS integrator can attend. In Delhi NCR, avoid optional changes during GRAP periods, when DG availability and compliance evidence are most sensitive.
Good answer sounds like: “Recommended, not mandatory. You can defer it to your annual shutdown without any loss of function.”
Does this update affect the type-approved configuration or emission performance?
Why it matters: CPCB’s system for compliance testing of retrofit emission control devices requires type approval with at least 70% particulate matter capture efficiency, carried out through recognised agencies such as ARAI or ICAT. If firmware controls regeneration timing, heater set points or anything affecting filtration, you need to know whether the change could affect the approved configuration. You can review the regulator’s material on the CPCB website and our explainer on reading an RECD test certificate.
Good answer sounds like: “The update changes logging and communication only. It does not alter regeneration logic, heater set points or anything in the type-approved configuration. We will confirm that in writing on our letterhead.”
Ask for that written confirmation every time. A verbal “no effect” is not evidence in an SPCB inspection or audit.
Round 2: “What Changes” Questions
Will any alarm thresholds, delays or set points change?
Why it matters: A new default high-ΔP threshold or a longer alarm delay alters when operators are warned. A delay raised from 30 to 120 seconds may be sensible, but operators and BMS logic must know.
Good answer sounds like: “Threshold values stay as configured. The only change is a new 60-second debounce on the sensor fault alarm, which we will show you on the parameter list.”
Will sensor scaling, ranges or engineering units change?
Why it matters: This is the commonest source of trouble after an emission control controller update. If the transmitted unit or decimal places change, every downstream system that assumed the old format will be wrong. Our guide on specifying replacement RECD sensors shows how scaling errors hide behind plausible numbers; firmware can cause the same problem without any hardware change.
Good answer sounds like: “ΔP will now be logged in mbar instead of kPa, with one decimal place. The Modbus register value is multiplied by 10 compared with before. Your BMS scaling will need updating.”
Does the data log format change?
Why it matters: A new column order or date format will break spreadsheet or platform imports. Ask whether old logs are retained or wiped.
Good answer sounds like: “The column order is unchanged. Timestamps move from DD-MM-YY to ISO 8601 format. Existing logs stay on the card and remain readable.”
The ISO 8601 date and time format is sensible, but a switch to it still needs planning.
Does the Modbus or BMS register map change?
Why it matters: BMS integration after a firmware update fails most often because a register moved, changed data type or changed byte order. The BMS keeps polling and shows something, which is worse than nothing.
Good answer sounds like: “Here is the old and new register map side by side. Registers 40001 to 40012 are unchanged. Two new status registers are added at 40020 and 40021.”
Will any settings reset to factory defaults?
Why it matters: Some updates wipe user parameters such as tuned thresholds, communication addresses and baud rates. If the Modbus address resets to 1 and your BMS expects 7, communication silently stops.
Good answer sounds like: “The update preserves user parameters, but we will export them first and re-import them if anything resets. We will compare the list before and after.”
What happens to the controller clock and time zone?
Why it matters: Logs are only evidence if timestamps are trustworthy. A reset clock or wrong time zone can shift every record by five and a half hours against IST, breaking correlation with DG run hours, your RECD shift handover log or GRAP-period records very difficult.
Good answer sounds like: “The clock is kept by a backup battery and is not affected. We will check it against a reference and set the time zone to IST after the update.”
Round 3: “How” Questions
Will you back up current settings and logs before the update?
Why it matters: A backup of controller settings before the update is your only route back if parameters are lost, and proof of the starting point. Ask for a parameter export and log copy left with you, not only on the technician’s laptop.
Good answer sounds like: “We export the full parameter file and all logs before starting, give you a copy on a fresh, scanned USB drive or by email, and note the file names on the service report.”
Will you record version numbers before and after?
Why it matters: “Firmware updated” on a service sheet tells an auditor nothing. You need controller model, hardware revision, and exact versions and builds before and after. Our article on auditing an RECD service report for missing information explains why vague entries create problems months later.
Good answer sounds like: “Before: 2.1.4, build 0712. After: 2.3.0, build 0905. Both will be photographed from the controller’s ‘About’ screen and written on the report.”
Who will perform the update, and with what tools?
Why it matters: You want a named person trained on that controller family, using the supplier’s approved tools. Ask whether the update is local or remote, and who approves remote access.
Good answer sounds like: “Our controls engineer, experienced on this model, attends with our licensed tool and cable. No remote access.”
How do you keep the laptop and USB drives free of malware?
Why it matters: A laptop that moves between dozens of sites can carry malware into a controller and onward to your BMS. Good practice: a dedicated service laptop with current antivirus, scanned USB drives, no personal browsing, and firmware files from the manufacturer with a verified checksum.
Good answer sounds like: “A dedicated, managed laptop, checksum-verified files, and scanned USB drives.”
Share any site IT or OT security policy beforehand. Our article on RECDs for data centres shows how such sites plan interventions around redundancy.
Must the DG set be stopped, and for how long?
Why it matters: Most updates should be done with the engine stopped and the exhaust cool. Agree the outage window, arrange standby power if needed, and apply lockout and tagout to the DG start circuits. If engine work is planned, combine outages; see coordinating DG engine repairs with the RECD service team. The principles of controlling hazardous energy are a useful reference even outside the US.
Good answer sounds like: “The DG must be stopped and locked out. The update takes about 20 minutes, plus 40 minutes for backup and verification. Plan for a 90-minute window.”
Is the controller power supply stable enough for flashing?
Why it matters: A power interruption mid-flash can leave a controller unbootable, so check supplies fed from a battery charger or shared UPS. Our guide to RECD controller and heater power supply requirements explains what a clean supply looks like.
Good answer sounds like: “We will confirm the controller supply voltage before starting and make sure it is not on a circuit that switches during the work. If the supply is doubtful, we bring a temporary regulated supply.”
Round 4: “What If” Questions
What is your firmware rollback plan?
Why it matters: A firmware rollback plan answers one question: can we return to the old version, and how quickly? Some controllers block downgrades, so find out before you start.
Good answer sounds like: “Downgrade to 2.1.4 is supported. We carry the old firmware file and your parameter backup. A rollback takes about 15 minutes and is included in the visit.”
What happens if the update fails partway?
Why it matters: A “bricked” controller means no alarms or logs until recovered. Ask about on-site recovery, a spare controller, and interim operation. Never accept a suggestion to bypass or disconnect the RECD itself to keep the DG running; that is a compliance risk, not a workaround.
Good answer sounds like: “The controller has a recovery bootloader we can use on site. If that fails, we carry a pre-configured spare. In the meantime the filter remains in the exhaust path and we agree manual checks with your operators.”
Does the update affect warranty?
Why it matters: Terms may exclude faults from unapproved software, or from refusing a mandatory update. Read our article on RECD warranty terms, parts, labour and exclusions.
Good answer sounds like: “The update is performed by us and keeps your warranty intact. We will note it on the service report so it is part of the warranty record.”
Who pays if something goes wrong?
Why it matters: Someone pays for return visits, integrator time and parts if things break. Agree this before the visit.
Good answer sounds like: “If the fault arises from our update, we cover the return visit, any controller replacement and up to one visit by your BMS integrator to remap registers we changed.”
What if the controller model is near end of support?
Why it matters: An update may be the model’s last. If it is being phased out, read our guide on planning for parts and support when an RECD model is discontinued.
Good answer sounds like: “This is the final planned release for this controller family. Support continues for five years, and a drop-in replacement controller exists. We can quote it now if you want it on the shelf.”
Round 5: “After” Questions
A firmware change is not finished at 100% on the progress bar. It is finished when you have proved the system still does what you need.
What verification tests will you run after the update?
Why it matters: At minimum: the controller boots, reads every sensor plausibly, logs with correct timestamps and talks to the BMS. Get the test list in advance.
Good answer sounds like: “We check each input against a reference, the log and every BMS point. You witness and sign.”
Will you prove that alarms actually trigger?
Why it matters: An untested alarm is an assumption. Simulate each critical alarm with a test signal, confirm it locally, in the log and on the BMS, then restore settings. Use calibrated instruments; see our post on RECD test instrument calibration records.
Good answer sounds like: “We inject a test signal for high ΔP and high temperature, confirm each alarm reaches your BMS within the expected delay, then restore and record the original thresholds.”
Will you check every BMS point, not just a sample?
Why it matters: One register may move while the rest stay put. Check every point on controller and BMS at the same moment, with units.
Good answer sounds like: “We will go through the point list with your BMS team line by line and record both readings side by side.”
Will you compare readings before and after at a stated load?
Why it matters: The best proof that scaling is unchanged is a like-for-like comparison at the same stated load and warm-up before and after. Our article on why generator load must be matched for RECD comparisons explains why load matters so much.
Good answer sounds like: “We will run the DG at 60% load for 20 minutes before and after, note ΔP and outlet temperature both times, and explain any difference.”
If the design uses active regeneration, avoid taking comparison readings during a regeneration event. Our guide to what to record during regeneration shows why readings swing at those times.
What documentation will we receive?
Why it matters: The update must enter your records, including updated drawings if panel wiring changed. Our sibling article on updating RECD drawings and records after modifications covers the drawing side of the same discipline.
Good answer sounds like: “Service report, parameter exports, release notes, new register map and written type-approval confirmation.”
Will you brief our operators on anything they will see differently?
Why it matters: Changed menus, alarm texts or units will otherwise be logged as faults on the next shift.
Good answer sounds like: “We brief your supervisor and leave a one-page summary at the panel.”
Illustrative Example: When kPa Became mbar
This example is illustrative.
A commercial building’s RECD controller transmits filter ΔP to the BMS through a Modbus register. Before the update, the register holds ΔP in kPa multiplied by 10, so the BMS divides the raw value by 10 and labels it “kPa”. The BMS high-ΔP alarm is set at 3.0 kPa.
The firmware release notes mention, in one line, that ΔP is now logged and transmitted in mbar “for better resolution”. Nobody updates the BMS.
Before the update, with the DG at 60% load and the filter moderately loaded:
- Actual ΔP: 1.8 kPa
- Raw register value: 1.8 × 10 = 18
- BMS calculation: 18 ÷ 10 = 1.8, shown as 1.8 kPa. No alarm.
After the update, same load, same filter condition:
- Actual ΔP is still 1.8 kPa. Since 1 kPa = 10 mbar, that is 1.8 × 10 = 18 mbar.
- Raw register value (mbar × 10): 18 × 10 = 180
- BMS calculation, unchanged: 180 ÷ 10 = 18, shown as 18 kPa
- BMS alarm threshold is 3.0 kPa, and 18 is greater than 3.0, so the BMS raises a high-ΔP alarm.
The BMS now shows exactly ten times the true value. The 18 kPa reading is not real; the error factor is 18 ÷ 1.8 = 10, which matches the kPa-to-mbar conversion exactly.
How verification catches it
- Side-by-side point check. The controller display reads “18.0 mbar”. The BMS reads “18 kPa”. The numbers match but the units do not, and 18 mbar is 1.8 kPa. The mismatch is obvious within a minute if someone compares both screens with units.
- Before-and-after comparison at stated load. Before the update the BMS showed 1.8 kPa at 60% load; after, 18 kPa at the same load. A tenfold jump with no physical change points to scaling, not to a blocked filter.
- Release note review. The one-line note on units, read in Round 2, would have flagged the BMS change in advance.
The fix
Either change the BMS scaling so that 180 ÷ 100 = 1.8 kPa is displayed, or keep the BMS in mbar and change the label and threshold to 30 mbar (3.0 kPa × 10). Record which option was chosen in the change record.
The opposite danger
Had the change gone the other way, the BMS would show one-tenth of the true value, and a genuinely high ΔP would never alarm. Our article on how exhaust back-pressure affects a DG set explains why that silent failure is the more serious one.
Pre-Visit Checklist
Use this list in the week before the service visit.
- Release notes received for every version between current and target.
- Written confirmation requested that type-approved configuration and emission performance are unaffected.
- Old and new Modbus/BMS register maps received and compared.
- BMS integrator informed and available on the day, or on call.
- Current controller parameters and recent logs exported or photographed by your own team as a second copy.
- Current firmware version recorded from the controller screen.
- Outage window agreed; standby power arranged if needed.
- Lockout/tagout procedure for the DG start circuits ready.
- Controller power supply checked for stability.
- Rollback plan and failed-update plan confirmed in writing.
- Reference readings taken at a stated load before the visit, or scheduled for the start of the visit.
Post-Visit Verification Table
Complete this table with the technician before they leave site.
| Check | Method | Expected result | Result / initials |
|---|---|---|---|
| Firmware version | Photograph controller “About” screen | Matches target version and build | |
| Parameters retained | Compare before and after exports | No unplanned differences | |
| Clock and time zone | Compare with reference clock | Within 1 minute, IST | |
| Each sensor input | Compare with reference instrument | Within stated tolerance | |
| Data log entry | Force or wait for new entry | New entry with correct timestamp and units | |
| High ΔP alarm | Test signal or temporary threshold | Local, log and BMS alarm, then reset | |
| High temperature alarm | Test signal or temporary threshold | Local, log and BMS alarm, then reset | |
| Every BMS point | Side-by-side controller vs BMS | Same value, same units | |
| Readings at stated load | Same load and warm-up as before | Differences explained | |
| Heater/regeneration status (if fitted) | Status screen and BMS | Correct state shown | |
| Operator briefing | Supervisor sign-off | Briefing given, summary at panel |
A Simple Change Record Template
Firmware change control on a DG set does not need heavy software. A one-page record, kept with the DG and RECD file, is enough for most sites. The general idea of configuration management, keeping a system’s settings and changes controlled and documented across its life, is described in the NIST glossary entry on configuration management.
| Field | Entry |
|---|---|
| Change record number | |
| Site and DG set ID | |
| RECD serial number and controller model | |
| Firmware version before (with build/checksum) | |
| Firmware version after (with build/checksum) | |
| Reason for change | |
| Release notes reference | |
| Type-approval / performance confirmation reference | |
| Parameters changed (list) | |
| Units, scaling or register map changes | |
| BMS changes made (by whom, date) | |
| Backup file names and storage location | |
| Rollback available (yes/no, method) | |
| Performed by (name, company) | |
| Verification table attached (yes/no) | |
| Readings before and after at stated load | |
| Approved by (site) | |
| Approved by (supplier) |
File it with the service report and update your asset register.
FAQ
Do all RECDs need firmware updates?
No. Many RECDs have no controller, or only a simple gauge or pressure switch, and never need software updates. Firmware questions only apply if your RECD has a controller with updatable firmware.
Can I refuse an RECD firmware update?
Usually you can defer an optional update. If the supplier says it is mandatory, ask for the reason in writing and check your warranty terms before refusing.
Will a firmware update affect my RECD’s CPCB type approval?
It should not, but only the supplier can confirm that for a specific update. Ask for written confirmation that the type-approved configuration and emission performance are unaffected.
Why does my BMS show wrong values after a firmware update?
The most common causes are a change of units or scaling, a moved Modbus register, a changed data type, or a reset communication address. Compare the controller display and the BMS side by side, with units.
Should the DG set run during the update?
Generally no. Most updates should be done with the DG stopped, locked out and the exhaust cool, with a stable controller power supply. Confirm the procedure with your supplier.
How long should we keep firmware change records?
Keep them for the life of the RECD, alongside service reports and test certificates. They help in audits, warranty claims and any future change of ownership.
Planning a Controller Update? Talk It Through with Aceget
Aceget supplies CPCB type-approved retrofit emission control devices for DG sets from 25 kVA to 2500 kVA and supports customers through installation, service and documentation. If you are preparing for a service visit and want to work through the questions above for your site, explore our retrofit emission control device range, review our certifications, or contact the Aceget team to discuss your DG set and monitoring set-up.
Related Reading
- How to Audit an RECD Service Report for Missing Information
- When an RECD Model Is Discontinued: Planning for Parts and Support
- Updating RECD Drawings and Records After Exhaust Modifications
- How to Specify Replacement RECD Sensors Without Losing Compatibility
- RECD Controller and Heater Power Supply Requirements
- RECD Test Instrument Calibration Records